Code Line Arrester for communication lines. Protection provided by heavy duty 3 electrode common chamber gas tube arrester connected across the lines to ground. Installation using AAR 2 3/8" terminal block. Protection starts at 500V peak, each line to ground and line to line.
Performance :
- Voltage breakdown either polarity :
- Less than 0.1 microsecond at 3 KV
- Less than 0.2 microsecond at 2 KV
- Less than 1.0 microsecond at 1.5 KV
- Arc voltage 20-30V.
- Life
Unlimited operations at 300 joules, 40KA, 8/20 µs. Maximum surge current 100 KA, 8/20 µs