Lightning Protection Corp.
P.O. Box 6086, Santa Barbara,
CA 93160 Phone: (800) 317-4043
phone: (805) 967-4577
Fax: (805) 967-4320
E-mail:
info@lightningprotectioncor.com
All Categories > Railroad > AC Power Circuits 60 to 100 Hz, 120 to 700 VAC -- Single and Three Phase > AC POWER CIRCUITS > Model LPC 90593-208-1  


Model LPC 90593-208-1, MOV type


Model LPC 90593-series

MOV type, single and three phase. 120 to 480VAC, 60-100 Hz. All mode protection, L-G, L-N, N-G, L-L. Surge current rating 100 KA per mode. Enclosure safety bonding lug. AAR binding post terminals. Insulating shields optional (see photo, typical L terminal). Series or T connection for unlimited load current. Metal enclosure 3” high; mounting base 2.5” X 6.5” with two mounting holes 0.265” D on 5.75” center (for standard mounting means).





 Specifications 

System Voltage

208 VAC

Number of Wires and Phases

3 wire and ground, 3 phase

MCOV

250 VAC, 3300 joules per mode.

Load

Series or T connection for unlimited load current.

Mounting

Mounting two holes 0.265” D on 5.75” center (for standard mounting means).

Protection

line to line and each line to ground protection.

Maximum Surge Current

100 KA per mode



Print Back